Alufire System

Home / Alufire System

Alufire System

Aluminium fire rated doors, windows, partitions EI 15, EI 30, EI 60, EI 120

  • The ALUFIRE system consists of fire rated composite glass sheet secured in aluminium profiles interconnected with a glass fibre reinforced polyamide thermal separator. The profile chambers are filled with silicate-cement inserts and intumescent seals are included at meeting surfaces. This enables the product to provide thermal insulation, and the required smoke and fire resistance that protects against the high temperatures created during a fire.
  • ALUFIRE System
  • ALUFIRE System
  • ALUFIRE System
  • ALUFIRE System
  • ALUFIRE System

 

  • Both glazed and non-transparent panels comply with EN fire resistance to the following classes EI 15, EI 30, EI 45, EI 60, and EI 120. Technical approval No. 15-6520/2010 issued by the Building Research Institute (ITB, Member of EOTA, UEAtc).
  • Alufire EI 30 and EI 60 Fire Doors conform to the ‘Heavy’ and ‘Very Heavy’ durability criteria required by EN 1192.
  • Doors can be supplied incorporating any or all of the following: Automatic swing door opener, Electromagnetic Lock (Reverse and Averse), Self –closer, smoke detector, electromagnetic catch and or Anti-panic levers.
  • Our doors can also be fitted with automatic cold smoke threshold seals to the bottom of the door, removing the requirement for raised thresholds. These are ideal for healthcare buildings and buildings requiring smooth floor surfaces and comply with EN 13501-2 Sa & Sm for control of smoke leakage.
  • Due to the highly engineered and robust construction our systems have arguably the highest acoustic coefficient on the market: Rw=41dB (RA1=41dB, RA2=38dB) for the internal constructions and Rw=44dB (RA1=43dB, RA2=40dB) for external constructions (according EN 20140-3).
  • Alufire fire rated partitions and doors can be manufactured in many bespoke shapes to suit the building requirements and can be supplied to closely match any RAL Colour.
  • Fire Rated Glazed Partitions can be installed in continuous segments not exceeding 4.0m in height by any length and can contain one single or double leaf door. (If vertical profiling spacing / one module does not exceed 1500mm) Complies with ETAG 0003, IVth use category.
  • Due to the impact resistance (hard, soft or heavy body) Alufire can be used in areas where there is an increased risk of accidents, improper use, or falling (e.g. from a floor above) Ideal for schools and other high traffic buildings.

Maximum Dimensions

Alufire fire rated glazing systems dimensions